Short characteristics:Smaller outdoor transformer substation – serviceable from the interior. Reinforced concrete body shell.
Basic specifications:- Outside length: 3.200 mm
- Outside width: 2.710 mm
- Height (over the ground): cca 2.630 mm
- Burring depth: 670 mm
- Total height: 3.300 mm
- Total weight (excluding the technology): cca 13 t
- Inner volume: 16,19 m3
- Ground coverage: 8,67 m3
- Max. transformer size: up to 630 kVA, (1600 kVA)
- Total volume of the reinforced concrete oil pan: approx. 2,24 m3 (1,49 x 2,510 x 0,6 m)
- HV switchgear: modular, compact (up to 4 bays)
- LV switchgear: up to 8 fuse disconnectors up to 400 A
- 2 all-aluminium doors (800 x 2000 + 1000 x 2000mm) with air grills at the bottom of both doors and cylinder locks
Substation gear assembly or replacement can be done either through the entrance doors or after lifting the detachable roof by a truck crane.