Short characteristics:Low, double, compact, semi-buried transformer substation – serviceable from the exterior. Reinforced concrete body shell.
Basic specifications:
- Outside length: 2.300 mm
- Outside width: 1.900 mm
- Height (over the ground): approx 1.910 mm
- Burring depth: 700 mm
- Total height: 2.610 mm
- Total weight (excluding the technology): approx 7,5 t
- Inner volume: approx. 8,4 m3
- Ground coverage: approx. 4,37 m3
- Max. transformer size: up to 630 kVA
- Total volume of the reinforced concrete oil pan: approx. 0,55 m3 (1,7 x 1,3 x 0,25m)
- HV switchgear: compact (up to 3 bays)
- LV switchgear: up to 8 fuse disconnectors up to 400 A
- 1 all-aluminium two-wing door (approx. 1540 x 1140 mm) with air grills at the top and a cylinder lock
- 1 (alternative A) or 2 (alternative B) all-aluminium doors (760 x 1140 mm) with air grills covering the entire surface (of the transformer and LV switchgear room) and cylinder locks
Substation gear assembly or replacement can be done after lifting the detachable roof by a truck crane.