Short characteristics:Low, compact, semi-buried transformer substation – serviceable from the exterior. Reinforced concrete body shell.
Basic specifications:- Outside length: 3.000 mm
- Outside width: 1.900 mm
- Height (over the ground): approx 1.910 mm
- Burring depth: 700 mm
- Total height: 2.610 mm
- Total weight (excluding the technology): approx 9,8 t
- Inner volume: approx. 14,8 m3
- Ground coverage: approx. 5,7 m3
- Max. transformer size: up to 630 kVA
- Total volume of the reinforced concrete oil pan: approx. 0,55 m3 (1,7 x 1,3 x 0,25 m)
- HV switchgear: compact (up to 4 bays)
- LV switchgear: up to 8 fuse disconnectors up to 400 A
- 2 all-aluminium two-wing doors (approx. 1540 x 1140 mm) with air grills at the top and cylinder locks
- 1 all-aluminium door (760 x 1140 mm) with the air grills covering the entire door surface and cylinder lock
Substation gear assembly or replacement can be done after lifting the detachable roof by a truck crane.